KS800-A/V

The KS800-A/V digital display is matched with various types of analog output sensors and transmitters to complete the measurement, transformation, display and control of physical quantities.


Error is less than 0.5% F.S, with calibration, digital filtering founction


Suitable for standard voltage and current signal types


Two point alarm output, upper limit alarm or lower limit alarm mode is optional. Alarm sensitivity can be independent setting


Transmission output (optional), can output measured and changed display values in standard current and voltage for other equipment.


Download
  • parameters
  • size
  • method

Power Supply  85V-265V AC and power consumption is less than 6W 

Note: The DC power supply should have a certain power margin. Please configure the power supply for each 24VDC/0.5A. Also pay attention to the length of the power cord and the wire diameter.

    Working environment  0°C-50°C, humidity below 90% R. H and no condensation.

    Display range -1999~9999, the decimal point position can be set

    Input signal type  current and voltage input, can be selected by parameter setting 

★Note: 0-10V DC input when ordering or changing by user. Open the instrument case, and the back of the instrument main board (the input signal terminal is on the circuit board) (The reverse side of the component) Cut the connection between SL1, and then the input signal selection parameters can be modified. At this time, the meter can only input voltage signal.



Input Signal Type

Measurement Stroke

Input Signal Type

Measurement Stroke

Voltage

 

0~5VDC

 

 

-1999~9999

Current

 

4~20mA

 

 

-1999~9999

 

1~5VDC

 

0~10mA

 

0~10VDC

 

0~20mA


   Basic error: less than 0.5% F.S

  Measurement control period: 0.2 seconds

   Alarm output: 2-point relay output, contact capacity 220V AC, 3A

--Transmitter output - photoelectric isolation, output resolution 1/3000, error less than ±0.2% FS

   -- DC current output, can be selected by setting 4mA~20mA, 0mA~10mA, 0mA~20mA.DC voltage output, you can select 1V~5V, 0V~5V by setting. 

      Note: 0V~10V transmission output, please indicate when ordering

--External power supply — used to supply power to the transmitter. The error between the output value and the nominal value is less than ±5%. 

   Note: The external power supply of the instrument can only be used for sensors or transmitters that are connected to the meter.








Attention: